Siemens breaker panels, circuit breakers and fuses

11 reports to CPSC, the latest made Oct 12, 2018. A report isn’t a recall.

Watch it to hear when CPSC publishes new reports about it. CPSC’s own search, on saferproducts.gov

Watch and the shortlist are kept with a free account, on every device. Your watch list. CPSC’s own search is on saferproducts.gov.

At a glance

From SaferProducts.gov, released Oct 25, 2026.

  • 11reports to CPSC
  • Oct 12, 2018the latest report was made
  • Oct 11, 2011the earliest
  • 0with the company’s comments
Brand
Siemens
Makers
SIEMENS INDUSTRY INC, SIEMENS ENERGY & AUTOMATION, INC. and Siemens Industr Inc.Makers, importers or sellers, as the reports name them
Product
Breaker panels, circuit breakers and fusesIncluding GFCIsCPSC’s product type: Panelboards, Circuit Breakers, Gfci”s, or Fuses (code 4063), in Home Maintenance and Structures: Electrical Systems
Other ways the reports write the brand (2)

“Seimens” and “Siemen’s”

By month

2 reports from November 2017 to October 2018; the most in October 2018, 1. 9 earlier reports, since October 2011, are in the table.
The numbers, as a table
Reports to CPSC by the month each was made, newest first
MonthReports
October 20181
January 20181
July 20161
April 20161
December 20141
October 20131
August 20132
August 20122
October 20111

How badly anyone was hurt

  • No one hurt 11 CPSC: Incident, No Injury

As each report says it, in short words; CPSC’s own words are under each.

The reports, as CPSC published them

Reports people made to the U.S. Consumer Product Safety Commission. CPSC publishes each one after sending it to the company named, and doesn’t guarantee they’re accurate. A report isn’t a recall.

Each report is the words of the person who made it, as CPSC published them. The company’s comments, where CPSC published any, are set apart as the company’s own.

Source:

CPSC, SaferProducts.gov public database export. Released Oct 25, 2026. Updated daily.

  1. No one hurt

    Made Oct 12, 2018, sent to the company Nov 20, 2018, published by CPSC Dec 6, 2018

    The product, in the report: Siemens circuit breaker

    I had problems with lights flickering in my home.After checking outlets and switches I went to the main entrance in the garage. I have a 200 amp siemens entrance panel with a100 amp amp sub feed to the house. As I was checking the incoming voltage on the main breaker , I noticed stray blue voltage coming from under the 100 amp sub feed breaker. At this time I focused my attention on this breaker and found it to be loose where it connects to the bus bar.

    At this time I shut off the main and removed it for inspection and found the feed terminals were both loose causing a poor connection to the bus bar. The lugs on the bus bar showed signs of overheating from arcing . At this time I went to Home Depot and purchased another 100 amp breaker and installed it and remedied the problem. I then found info about a recall on Siemens 15 - 50 amp breakers being faulty. I would like you to know it is also the 100 amp version also. This is a model Q2100 with a date code 0300.

    Model
    Q2100
    Bought from
    Home Depot
    Where
    Brasher Falls, New York: Home/Apartment/Condominium
    Who was involved
    Unknown
    The reporter’s relation to them
    Unspecified
    As this report names them
    Brand Seimens, made or sold by Siemens Industr Inc.
    How badly, in CPSC’s words
    Incident, No Injury
  2. No one hurt

    Made Jan 12, 2018, sent to the company Apr 11, 2018, published by CPSC Apr 25, 2018

    The product, in the report: Siemens panel 2 pole 40 amp breaker type QP, date label burnt off 200 amp main type EQ6895

    - our home has a 200 amp electrical panel - we noticed smoke coming from the panel at about 5:30pm 1/11/2018 - I opened the panel and turned off the main breaker before a fire started - the bottom left 2 pole 40 amp had heated up, melted, and caused other adjacent breakers to begin heating up - the bus bar got hot as a result of the breaker heating up and begin to melt the plastic panel board framework - the fire department checked for hot spots - the 20 pole 40 amp was hot and the 200 amp main was hot - the power company was told to come pull the meter and I was given instruction to have the panel replaced

    Where
    Burleson, Texas: Home/Apartment/Condominium
    Who was involved
    Age 45, Male
    The reporter’s relation to them
    Self
    As this report names them
    Brand Siemens, made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  3. No one hurt

    Made Jul 26, 2016, sent to the company Aug 5, 2016, published by CPSC Aug 19, 2016

    The product, in the report: Siemens breaker panel and 20Amp circuit breaker

    On July 18,16 we finally found the problem to what was causing our GFI circuit breakers from constantly tripping. This problem with the GFI breakings tripping has been going on about 2 weeks. Once we determined what was causing the GFI breakers to trip we started to have major power problems in part of out kitchen. In 2010 our whole apartment was gutted. All new electrical wires and a new breaker panel was installed. Once it was determined that one of the Siemens 20Amp circuit breakers’ had burnt contacts on the breaker and the stab of the buss bar. The power in the affected area was dropping to around 70VAC. Appliance’s don’t work well with this level of voltage. We have a damage microwave oven, coffee pot, remote appliance modules and a WiFi remote access point. I have been in contact with Siemens about the problem and I recently sent an email requesting some type of up date. The reference number of the case with Siemens is [REDACTED]. On your website you have listed a problems with these breaker but are under a different date code “Release #10-354”. The date code on my problem breaker is 0110. My concern is about a fire, I am a disabled veteran with mobility issues and with other family members in the 3 apartment house with disability issues, safety is a major concern now. I do have pictures of the problem but they are large in size in order to see the problem clearly. If you want the pictures just email me and I will sent them to you. But it will take several emails to get them all to you. If you want or need additional information email me and I will send you the information you want. I hope this information is getting to you because this is the third time and last time that I am going to type it up because the information keeps disappearing.

    Model
    breaker panel & 20Amp circuit breaker
    UPC
    783643148192
    Where
    Fall River, Massachusetts: Home/Apartment/Condominium
    Who was involved
    Male
    The reporter’s relation to them
    Self
    As this report names them
    Brand Siemens, made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  4. No one hurt

    Made Apr 7, 2016, sent to the company Apr 15, 2016, published by CPSC May 6, 2016

    The product, in the report: Siemens mobile home breaker panel

    Siemens M1020MB1100F Series C Type 1 L1495

    I have had problems for a year or two with breakers tripping constantly one week ago one did not trip and arced melted the hot bus bar and could have burned my mobile home down. It caused more breakers to trip and there is no way to fix it unless I replace the whole electrical box.

    Where
    Camden, Arkansas: Mobile/Manufactured Home
    Who was involved
    Age 31, Female
    The reporter’s relation to them
    Self
    As this report names them
    made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  5. No one hurt

    Made Dec 10, 2014, sent to the company Jan 14, 2015, published by CPSC Jan 29, 2015

    The product, in the report: 200 amp main circuit breakers

    Caller filed online incident report 12/09/2014 that wouldn’t complete.

    Siemen’s 200 amp main circuit breaker, model number and serial number not available at this time but information will be populated by caller before he returns his report. In 2010 CPSC recalled 2.2 million circuit breakers of various sizes.. Circuit breakers are four years old, installed in 2010 with no problems noted until caller was attempting to power his generator during a power outage on November 27th, 2014 and could not shut the breaker off in order to supply power to his home through the generator. The 200A breaker was confirmed defective by a licensed Electrician (Navsbaum Electric Perry N.H.)

    He is reporting this incident as a fire hazard because the breaker would not shut off.

    There have been no incidents of injury known at this time

    The manufacturer was contacted sometime around December 1st, 2014 and consumer was informed that he should return the breaker.

    He has already returned the breaker to the distributor and so cannot return it to the manufacturer.

    Model
    will be populated by consumer
    Serial number
    will be populated by consumer
    Bought from
    Home Depot, New Hampshire
    Bought
    Jun 15, 2010, about then
    Where
    Windham, New Hampshire: Home/Apartment/Condominium
    Who was involved
    Male
    The reporter’s relation to them
    Unspecified
    As this report names them
    Brand Siemens, made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  6. No one hurt

    Made Oct 23, 2013, sent to the company Oct 30, 2013, published by CPSC Nov 14, 2013

    The product, in the report: Arc Fault Current Interuptors

    Purchased a home in April 2013. Home built 2005. Tried to test the AFCI,s in accordance with instructions on electric panel board. Not one of the 3 AFCI,s would trip when test button pushed. Manufacturer. Siemens. AFCI serial Numbers. H0507280554, H 0507055748, H0507275049. I am concerned that these could be defective and pose a threat of injury or loss of life to persons depending on them for protection against fire caused by arcing of electrical system.

    Model
    Serial Numbers H0507280554, H0507055748, H0507275049
    Serial number
    see above
    Bought
    Jun 1, 2005, about then
    Where
    Ocala, Florida: Unspecified
    Who was involved
    Unknown
    The reporter’s relation to them
    Unspecified
    As this report names them
    Brand Siemens, made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  7. No one hurt

    Made Aug 12, 2013, sent to the company Sep 17, 2013, published by CPSC Oct 1, 2013

    The product, in the report: circuit breaker box

    (08/11/2013) The consumer stated that he and his wife were in the garage where the circuit box is located. The consumer stated that his wife said that she heard something buzzing. His wife walked over to the box and didcovered that the buzzing was coming from the circuit panel. The consumer stated that he open the panel and saw that it was arcing. He turned the main breaker off and the arcing and sparking stopped. He pulled the panel out and saw that one of the circuit breakers had melted. The consumer stated that the panel box is ruined on the right side.

    The consumer stated that he had the problem that was described in the recall rel#88-091. He stated that he was not notified of the recall.

    (08/12/2013) The consumer stated that he contacted the manufacturer and described what happened. He stated that he was advised that his model was not in the recall. The consumer stated that he was told that his product was 26 years old.

    Model
    M1986
    Bought from
    builder
    Bought
    Sep 1, 1986, about then
    Where
    Kevil, Kentucky: Home/Apartment/Condominium
    Who was involved
    Female
    The reporter’s relation to them
    My Spouse
    As this report names them
    Brand Seimens, made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  8. No one hurt

    Made Aug 5, 2013, sent to the company Aug 13, 2013, published by CPSC Aug 27, 2013

    The product, in the report: 2 pole Type QP 30A circuit breaker

    Siemens circuit breaker-- double 30A “2 pole Type QP” Household use-- connected to air conditioner. One pole tripped, but did not cause second pole to trip. This caused an overheat/arc situation, resulting in the spring clip of one pole breaker to melt to the busbar in the panel, and damage to the outer casing of the breaker.

    Model
    Q230 2 Pole Type QP
    UPC
    783643148383
    Bought from
    unknown
    Bought
    Mar 1, 2003, about then
    Where
    Ringwood, Illinois: Home/Apartment/Condominium
    Who was involved
    Unspecified
    The reporter’s relation to them
    Self
    As this report names them
    Brand Siemens, made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  9. No one hurt

    Made Aug 29, 2012, sent to the company Sep 11, 2012, published by CPSC Sep 25, 2012

    The product, in the report: Siemens Manufactured Housing Load Center Model #M1020MB1100F Series C Type 1

    I have a Siemens Load Center Model # M1020MB1100F in my home. I have had to replace three breakers (all three were quad breakers) due to the spring clips on the back of them losing connection with the buss bar and arcing. This breaker box has aluminum bus bars. The most frequent completely burned up the stab on the breaker box to the point it can not be used again. It also destroyed the breaker. I think this is directly related to the recall that I have read about but the recall does not list this breaker as one of concern. I do believe that this is a concern worth checking into. Thanks

    Model
    M1020MB100F
    Where
    Sanford, Texas: Mobile/Manufactured Home
    Who was involved
    Male
    The reporter’s relation to them
    Self
    As this report names them
    Brand Siemens, made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  10. No one hurt

    Made Aug 4, 2012, sent to the company Aug 23, 2012, published by CPSC Sep 7, 2012

    The product, in the report: Siemens electrical panel

    On Saturday, 7-28-12 I lost partial power to my pole barn. I went to my main fuse panel in the house and heard electrical sparking. I removed the face panel and could hear it was coming from a 60 amp breaker which fed my pole barn. I put a screwdriver on one of the screws and tightened and the sparking went away. On 7-29-12 at appx 6pm my compressor in the barn kicked on and I heard a loud crack. All of my power in the barn was out. I went downstairs to look at my panel. There was black residue on the panel cover. I removed the panel cover and noticed that both of the legs were black and the 60 amp breaker was tripped and angular. I checked voltage and there was none at the 60 amp breaker. I pulled the 60 amp breaker out, for replacement purposes, and the panel began to arc. I tried to pull the main, 200 amp breaker but it would not move. The panel is on fire and electricity continues to flow into the panel. The wires and breakers were burning. I used two fire extinguishers on the fire. The fire department responded and pulled the meter. If I had not been home I am sure the house would have caught on fire. Luckily the damage, smoke, was confined mostly to the basement of my home. I still have the damaged panel in my possession.

    Model
    G4040MB1200 Series .E Type 1
    Bought from
    electrician supplied panel
    Where
    Howard City, Michigan: Home/Apartment/Condominium
    Who was involved
    Unknown
    The reporter’s relation to them
    Unspecified
    As this report names them
    Brand Siemens, made or sold by SIEMENS INDUSTRY INC
    How badly, in CPSC’s words
    Incident, No Injury
  11. No one hurt

    Made Oct 11, 2011, sent to the company Oct 20, 2011, published by CPSC Nov 3, 2011

    The product, in the report: Siemens circuit breaker, date code: 0501; Model: EQ9675; 120/240 volt; 100 amps.

    Recently my husband & I were experiencing multiple electrical problems throughout our house. My husband heard electrical zapping coming from the circuit box. Upon checking the circuit box, we discovered electricity arcing several times a minute while we stood & watched. The circuit breaker had sustained burn damage & the red dividing clip had melted quite a bit. The breaker has been replaced & we haven’t experience any more problems. The date code on our bad breaker is 0501. We experienced the same issues as the recently recalled 2010 breakers.

    Model
    Model EQ9675
    UPC
    7-8364325538-8
    Serial number
    n/a
    Bought from
    unknown, Missouri
    Bought
    Jul 14, 2001, about then
    Where
    Florissant, Missouri: Home/Apartment/Condominium
    Who was involved
    Female
    The reporter’s relation to them
    Unspecified
    As this report names them
    Brand Siemen’s, made or sold by SIEMENS ENERGY & AUTOMATION, INC.
    How badly, in CPSC’s words
    Incident, No Injury

CPSC’s disclaimer

Disclaimer: CPSC does not guarantee the accuracy, completeness, or adequacy of the contents of the Publicly Available Consumer Product Safety Information Database on SaferProducts.gov, particularly with respect to information submitted by people outside of CPSC.

Source:

Word for word, from the disclaimer in CPSC’s export.

Sources

Sources
  • U.S. Consumer Product Safety Commission, SaferProducts.gov public database export.

    Released Oct 25, 2026 and checked Oct 25, 2026. Updated daily. Public domain (U.S. Government work). CPSC asks to be credited, and that no endorsement be implied.

Source:

Reports of harm are from the U.S. Consumer Product Safety Commission (CPSC), on SaferProducts.gov. CPSC does not endorse Hearth Record.

Back to Breaker panels, circuit breakers and fuses

How to read a record

Four things every record does, shown on an example record made up for this guide.

An example record, made up for this guide

An example nursing home

Made up for this guide: no real place is shown

Not fully inspected in over two years (CMS flag)

11 health citations at the latest inspection cycle

The state average is 14.3.

Source:

CMS, State and US Averages and Health Deficiencies. Released Oct 8, 2026. Updated monthly.

From the homeNone yet. Replies and paid listings aren’t open, and when they open they will sit here, below the record.

1 of 4

Every fact names its source.

Who published it, when, and how often it changes sit beside each fact, with a link to the agency’s own file.

Sign in

A free account keeps your watch list, shortlists, comparisons and saved searches on every device, and can email you when something you watch changes. Browsing never needs one.