Hearth Record

Siemens Recalls Circuit Breakers Due to Fire Hazard

Home product recall 10-354. Announced by CPSC on Sep 23, 2010.

CPSC’s own notice, on cpsc.gov

Watch and the shortlist are kept with a free account, on every device. Your watch list. CPSC’s own notice is on cpsc.gov.

The short answer

Announced by CPSC on Sep 23, 2010. Copied from CPSC on Oct 19, 2026.

Every line below is in CPSC’s own words, with its source beside it.

What’s wrong with it?

The recalled circuit breakers have a spring clip that can break during normal use, leading to a loss of force to maintain a proper electrical connection in the panelboard. This can lead to excessive temperature, arcing or thermal damage at the connection point, and damage to the panelboard’s electrical insulation and can result in a fire, property damage, or personal injury.

Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

What should you do?

Consumers should immediately contact Siemens for a free inspection by an electrician and a free replacement product.

Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

  • How to reach the firm: For additional information, contact Siemens at (800) 756-6996 between 9 a.m. and 5 p.m. ET Monday through Friday or visit the firm’s website at www.usa.siemens.com

Which ones are recalled?

This recall involves Siemens and Murray 15 through 50 AMP single and double pole circuit breakers, load centers (circuit breakers that come with an electrical panel), and meter combos (contain a load center and a meter socket). “Siemens” or “Murray,” date codes 0610 or 0710 and the catalog number are printed on a label on the side of the circuit breakers. Date codes between June 2010 through August 2010 are stamped on the inside of the metal box of the load centers and meter combos. The catalog number for the load centers and meter combos is printed on a label inside the metal box door and on the packaging. Product Date Codes Catalog Numbers Circuit Breakers 0610, 0710 Q115, Q120, Q130, Q215, Q230, Q250, MP115, MP115U, MP120, MP130, MP215, MP230, MP230U, MP250 Load Centers Jun 23 2010 - Aug 25 2010 G2020B1100CP, G3030B1100CP, G4040B1200CUSGP, LC4040B1200P, G3040B1200CP, G3040L1200CP, G4040B1200CP, G3030B1150CP, W3040B1200CP, G1624L1125CP, W4040B1200CP Meter Combo Jun 23 2010 - Aug 25 2010 JA2040B1200S

About 2.2 million units, as CPSC gives them.

Siemens and Murray Circuit Breakers, Load Centers and Meter Combos.

Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

CPSC’s photos

CPSC shows 4 photos on its notice. Hearth Record doesn’t copy them; each opens on cpsc.gov.

Who made and sold it?

  • Imported by Siemens Industry Inc., Alpharetta, Ga.
  • The Home Depot, Lowes, other hardware and building supply stores and numerous electrical distributors nationwide from June 2010 through August 2010 for between $2.50 to $235.
  • Made in Mexico, as the notice gives it.
Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

Was anyone hurt?

Siemens has received one report of a circuit breaker spring clip that broke during installation. No injuries have been reported.

Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

What the record doesn’t say

  • The notice lists no UPCs, so check the model, the description and the photos.
  • The notice lists no model numbers in a field of their own; its description may give them.
  • How many have been returned or fixed isn’t in the notice.
Source:

Hearth Record wrote these lines.

Sources

  • U.S. Consumer Product Safety Commission, Recalls API.

    Checked Oct 19, 2026. Updated daily. Public domain (U.S. Government work). CPSC asks to be credited, and that no endorsement be implied.

Source:

Recalls of kids’ and home products are from the U.S. Consumer Product Safety Commission (CPSC). CPSC does not endorse Hearth Record. Copied on Oct 19, 2026.

How to read a record

Four things every record does, shown on an example record made up for this guide.

An example record, made up for this guide

An example nursing home

Made up for this guide: no real place is shown

Not fully inspected in over two years (CMS flag)

11 health citations at the latest inspection cycle

The state average is 14.3.

Source:

CMS, State and US Averages and Health Deficiencies. Released Oct 8, 2026. Updated monthly.

From the homeNone yet. Replies and paid listings aren’t open, and when they open they will sit here, below the record.

1 of 4

Every fact names its source.

Who published it, when, and how often it changes sit beside each fact, with a link to the agency’s own file.

Sign in