Hearth Record

CPSC, Schneider Electric North American Division Announce Recall of AFCIs

Home product recall 05-035. Announced by CPSC on Nov 3, 2004.

CPSC’s own notice, on cpsc.gov

Watch and the shortlist are kept with a free account, on every device. Your watch list. CPSC’s own notice is on cpsc.gov.

The short answer

Announced by CPSC on Nov 3, 2004. Copied from CPSC on Oct 19, 2026.

Every line below is in CPSC’s own words, with its source beside it.

What’s wrong with it?

An AFCI is an electrical circuit protection device (circuit breaker) that detects electrical arcs from cracked, broken or damaged electrical insulation and shuts off power to the circuit before the arcing leads to a fire. An electronic component failure inside the AFCIs can cause the devices to not detect an electrical arc. Although the AFCIs will function as regular circuit breakers, they may not detect an arc fault, posing a safety risk to consumers.

Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

What should you do?

Installed AFCIs will be replaced free of charge through electrical contractors. Consumers can return uninstalled AFCIs to the retailers or distributor from whom the unit was purchased for a free replacement unit.

Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

  • How to reach the firm: Consumers should call the Customer Care Center Number “888 SQUARED” or 888-778-2733 to return the product for replacement or refund. Consumers can also call 1-800-634-8730 and ask for the Product Services Support Manager.

Which ones are recalled?

The recalled Square D QO® and Homeline® Arc Fault Interrupter circuit breakers are used with 15- and 20-amp branch circuits. They are required to be installed in bedroom circuits in accordance with the 2002 National Electrical Code. The recalled units were manufactured after March 1, 2004, and have a blue test button. The AFCI circuit breakers have one of the following date codes - CN, DN, EN, FN, GN, HN, or JN - stamped in red on the breaker label located just above the wiring terminal. The recalled units also have one of the following catalog numbers printed on a label on the front of the breaker: QO115AFI, QO115AFIC, QO120AFI, QO120AFIC, QOB115AFI, QOB120AFI, HOM115AFI, HOM115AFIC, HOM120AFI, HOM120AFIC, QO115VHAFI, QO120VHAFI, QOB115VHAFI, or QOB120VHAFI.

About 700,000 units, as CPSC gives them.

Arc Fault Circuit Interrupters (AFCI).

Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

CPSC’s photos

CPSC shows 2 photos on its notice. Hearth Record doesn’t copy them; each opens on cpsc.gov.

Who made and sold it?

  • Made by Schneider Electric North American Division, Palatine, Ill.
  • Electrical distributors and retailers sold the AFCIs between March 2004 and September 2004 for between $30 and $130.
  • Made in Mexico, as the notice gives it.
Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

Was anyone hurt?

Schneider Electric is investigating one reported fire during a new home construction that may be related to this problem. No injuries have been reported.

Source:

CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.

What the record doesn’t say

  • The notice lists no UPCs, so check the model, the description and the photos.
  • The notice lists no model numbers in a field of their own; its description may give them.
  • How many have been returned or fixed isn’t in the notice.
Source:

Hearth Record wrote these lines.

Sources

  • U.S. Consumer Product Safety Commission, Recalls API.

    Checked Oct 19, 2026. Updated daily. Public domain (U.S. Government work). CPSC asks to be credited, and that no endorsement be implied.

Source:

Recalls of kids’ and home products are from the U.S. Consumer Product Safety Commission (CPSC). CPSC does not endorse Hearth Record. Copied on Oct 19, 2026.

How to read a record

Four things every record does, shown on an example record made up for this guide.

An example record, made up for this guide

An example nursing home

Made up for this guide: no real place is shown

Not fully inspected in over two years (CMS flag)

11 health citations at the latest inspection cycle

The state average is 14.3.

Source:

CMS, State and US Averages and Health Deficiencies. Released Oct 8, 2026. Updated monthly.

From the homeNone yet. Replies and paid listings aren’t open, and when they open they will sit here, below the record.

1 of 4

Every fact names its source.

Who published it, when, and how often it changes sit beside each fact, with a link to the agency’s own file.

Sign in

A free account keeps your watch list, shortlists, comparisons and saved searches on every device, and can email you when something you watch changes. Browsing never needs one.