CPSC, Trane Company Announce Recall of Voyager Heating and Air Conditioning Systems
Home product recall 01-507. Announced by CPSC on Jan 24, 2001.
Watch and the shortlist are kept with a free account, on every device. Your watch list. CPSC’s own notice is on cpsc.gov.
The short answer
Announced by CPSC on Jan 24, 2001. Copied from CPSC on Oct 19, 2026.
Every line below is in CPSC’s own words, with its source beside it.
What’s wrong with it?
One of the three internal flue gas tubes extending from the heat exchanger can separate from the heat exchanger. This could allow flue gases, including carbon monoxide, to enter the building airstream. This could result in serious injury or death to building occupants.
CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.
What should you do?
Call the local independent Trane or American Standard dealer for a free inspection and replacement, if needed. Trane will completely replace the heat exchanger end plate and internal flue gas tube assemblies in all recalled units at no cost to the consumer.
CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.
- How to reach the firm: For assistance in locating a local independent dealer, contact Trane at (800) 940-1344 between 7:30 a.m. and 4:30 p.m. CT Monday through Friday, or visit the firm’s web site at www.trane.com
Which ones are recalled?
The Voyager series of light commercial rooftop air conditioners with electric cooling and gas-fired heat exchangers, which are installed in schools and commercial applications, have 120,000 to 135,00 BTU heating capacity and three- to five-ton cooling capacity in horizontal and downflow configurations. The Voyager series has been manufactured by Trane since 1988 and is distributed under the Trane® and American Standard® brand names. The recalled units were manufactured between June 1, 2000 and August 16, 2000 and have serial numbers beginning with R21 through and including R33. The recalled products include the following model designations: YCD036C1H_ _ _ YCD060CWH_ _ _ YCD048C1H_ _ _ YCH060C1H_ _ _ YCH048C1H_ _ _ YCH060C3H_ _ _ YCD060C1H_ _ _ YCH060C4H_ _ _ YCD060C1H_ _ _ YCD060C3H_ _ _ YCD060C4H_ _ _ A name plate bearing each unit’s model and serial number is located on the outside sheet metal at the end of the unit where the propeller fan is visible on top, directly to the left of the exposed outdoor coils.
967 units, as CPSC gives them.
Trane Voyager Series Combination Gas Furnace and Electric Air Conditioning Units.
CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.
CPSC’s photos
CPSC shows 1 photo on its notice. Hearth Record doesn’t copy them; each opens on cpsc.gov.
Who made and sold it?
- Made by The Trane Company, Tyler, Texas, a division of American Standard Companies Inc.
CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.
Was anyone hurt?
None reported.
CPSC, Recalls API. Checked Oct 19, 2026. Updated daily.
What the record doesn’t say
- The notice lists no UPCs, so check the model, the description and the photos.
- The notice lists no model numbers in a field of their own; its description may give them.
- How many have been returned or fixed isn’t in the notice.
Hearth Record wrote these lines.
Sources
-
U.S. Consumer Product Safety Commission, Recalls API.
Checked Oct 19, 2026. Updated daily. Public domain (U.S. Government work). CPSC asks to be credited, and that no endorsement be implied.